Diesel Fuel Storage for Generators: Guide

Diesel Fuel Storage for Generators: Guide

Storing diesel fuel properly is critical for ensuring your generator works when you need it most. Poor storage can lead to fuel degradation, contamination, and generator failure. Here's what you need to know:

  • Diesel Shelf Life: Typically 6–12 months, but proper storage can extend this to 3+ years.
  • Tank Sizing: Calculate fuel needs based on generator consumption, runtime, and safety margins.
  • Tank Types: Options include above-ground, underground, sub-base, and day tanks, each with specific pros and cons.
  • Fuel Quality: Regular testing, stabilizers, additives, and filtration prevent issues like microbial growth and water contamination.
  • Safety Measures: Follow local regulations, ensure proper ventilation, and maintain fire safety equipment.
  • Emergency Planning: Keep enough fuel for outages, diversify suppliers, and monitor fuel levels to avoid shortages.

Proper storage, regular maintenance, and compliance with safety standards ensure your generator performs reliably during emergencies.

Diesel Fuel Tanks on Generators

Tank Sizing and Selection

Picking the right tank size and type for your diesel generator is a critical step to ensure reliable power during emergencies. A poorly chosen tank can leave you stranded when you need power the most. Accurate sizing guarantees your generator has enough fuel to operate seamlessly. Start by calculating your fuel needs before deciding on the best tank type.

How to Calculate Tank Size

To determine the right tank size, you need to know your generator's fuel consumption rate. On average, generators use around 0.1 gallons per hour for every kilowatt of output. However, always check your generator's specification sheet for exact numbers, as fuel consumption rates can vary widely between models and manufacturers.

Once you have the consumption rate, multiply it by the desired runtime. Add a 10–20% safety margin and account for unusable capacity due to fuel expansion. For instance, if your generator consumes 5.3 gallons per hour and you need an 8-hour runtime, the calculation would look like this: (5.3 gal/h × 8 h × 1.15) ÷ 0.85 ≈ 57 gallons. This ensures you have enough capacity to handle operational needs and safety requirements.

The NFPA 20 standard offers guidelines for fuel tank sizing:

"Per NFPA20 2022 11.4.1.3.1 Fuel supply tank(s) shall be sized for a minimum of 12 hours of engine run time based on the fuel supply rate requirements of the engine, plus 5% volume for expansion and 5% volume for sump."

If the engine's fuel consumption rate is unavailable, NFPA 20 provides an alternative calculation method:

"Per NFPA20 2022 11.4.1.3.1.1 When the fuel supply rate requirements of the engine are not known, fuel supply tank(s) shall have a capacity at least equal to 1 Gal/HP (5.07L/kW), plus 5% volume for expansion and 5% volume for sump."

For practical planning, arrange for refueling within 24 hours if your expected runtime is 48 hours or less. For shorter runtimes, ensure your tank can support at least 24 hours of continuous operation.

Tank Types and Options

Diesel fuel storage tanks come in various configurations, each with distinct features and compliance requirements.

  • Above-ground steel tanks: Most meet UL-142 standards, which ensure safety for flammable liquids. Look for tanks marked with the UL symbol and the word "LISTED".
  • UL-2085 tanks: These offer advanced safety features, including two-hour fire resistance, secondary containment, and projectile resistance. While pricier, they provide enhanced safety.

Your installation method will depend on available space, environmental factors, and local regulations. Above-ground tanks require emergency relief venting and spill control systems, while underground tanks need external corrosion protection.

The choice between single-wall and double-wall tanks hinges on local regulations and environmental concerns. Double-wall tanks include built-in secondary containment, often eliminating the need for separate containment systems.

Codes and Standards

Compliance with regulations is essential for safety and legal adherence. Storage requirements depend on whether the fuel is classified as "combustible" or "flammable", which is determined by its flash point. Standard diesel is typically combustible, but blends like E-diesel (with ethanol) are flammable and require different safety measures.

Several key codes govern diesel fuel storage:

  • NFPA 30: Covers flammable and combustible liquids, including separation distances to prevent fire spread.
  • NFPA 110: Requires Class 48 emergency power supply systems (EPSS) to operate for at least 48 hours without refueling. The tank must hold at least 133% of the fuel needed for the EPSS class.
  • API Standard 650: Addresses welded tanks for oil storage.

OSHA also mandates a 10B-rated fire extinguisher within 50 feet of storage areas and requires fuel to be stored in approved containers.

Local regulations may impose stricter rules than national standards. States like California, Colorado, Florida, and Texas often have additional requirements. It's wise to consult your local fire marshal to confirm compliance with UL standards and any specific local mandates.

If you opt for a custom tank, ensure it comes with documentation proving it meets all relevant standards. Partnering with experienced suppliers familiar with these regulations can help streamline the process and prevent compliance issues during installation.

Fuel Quality Management

Poor fuel quality can seriously impact a generator’s performance. Issues like water contamination, microbial growth, and fuel degradation can clog filters or even lead to engine failure. The good news? Regular monitoring and maintenance can help keep your fuel in top condition.

Testing and Monitoring

Routine fuel testing is essential to prevent generator issues. In the UK, regulations recommend testing fuel four times a year if no fuel polishing system is used, as outlined in the BS 5410-3:2016 standard. With a fuel polishing system, testing can be reduced to twice annually.

Start by visually inspecting fuel filters and sampling the tank bottom to check for contaminants. Diesel fuel’s appearance can reveal its quality - clean diesel is typically clear to amber, while cloudy fuel or visible particles suggest contamination.

For detecting microbial contamination, several testing methods are available:

Test Type Detection Location Time to Result Pros Cons
CFU Testing All microbes Lab or on-site kit Days Identifies all microbes Time-consuming; may give misleading results
ATP Testing Living microbial cells Lab or on-site Varies Measures active cells Requires special tools; can mislead
Immunoassay Testing (FUELSTAT®) Harmful microbes only On-site 15 minutes Quick and easy; targets harmful microbes Limited to specific microbes

On-site testing often provides faster results, reducing the risk of sample degradation during lab delays. According to Stewart Barrett, a Laboratory Scientist at Energy and Environmental Microbiology Services, microbial contamination is especially common in FAME (biofuel) blends due to their tendency to attract water.

If contamination is identified, act quickly by applying specialized fuel cleansers and biocides to prevent further damage.

Stabilizers and Additives

Fuel stabilizers are essential for protecting diesel during storage. Diesel begins to degrade within months due to exposure to air, moisture, and temperature fluctuations. Products like STA-BIL Diesel Fuel Stabilizer can treat large volumes effectively, helping to prevent sludge, reduce oxidation, and remove water.

When choosing a stabilizer, ensure it’s formulated specifically for diesel and free from alcohol or harmful solvents. For the best results, add stabilizers to fresh fuel rather than trying to restore already-degraded fuel.

Multifunctional additives can also be a smart choice. These products not only stabilize fuel but also improve cetane levels, enhance lubricity, clean injectors, and disperse water. If microbial contamination has been an issue, biocides are indispensable - they kill existing microbes and prevent future growth. Look for stabilizers that demulsify water, as this makes water removal more effective.

Filtration and Water Removal

Water contamination is a major cause of generator issues, leading to corrosion, engine damage, and operational disruptions. Symptoms include misfires, rough idling, reduced power, hard starts, white smoke, and clogged filters.

To combat water contamination, install high-quality fuel filters and replace them as recommended by the manufacturer. Water separators and coalescing filters are particularly effective, capturing water droplets for easy drainage. Position these filters between the fuel tank and generator to catch contaminants early.

"Water in diesel fuel can result in rust particles entering the fuel, promote the growth of bacteria and microorganisms, and, more directly, cause premature wear and corrosion in fuel injectors and other engine parts." – AirDog®

Regularly drain water from the bottom of your tank using the drain plug. Keeping fuel levels high minimizes air space, reducing condensation risks.

For removing water, two types of additives are commonly used:

  • Emulsifiers: Keep water mixed in the fuel so it can pass harmlessly through the engine, making them ideal for on-vehicle tanks and biodiesel fuels.
  • Demulsifiers: Separate water from fuel for mechanical removal, which works best for larger-scale contamination when paired with a water separator.

To prevent moisture from entering, ensure tanks are tightly sealed and inspect regularly for leaks or damage. Using winterized diesel and fuel heaters in cold weather can prevent freezing, while a first-in, first-out strategy ensures older fuel is used before it degrades.

Storage Safety and Handling

Now that we've covered tank selection and fuel quality, let's dive into the essentials of safely managing your diesel storage. Proper handling and maintenance are critical to protecting workers, preserving equipment, and meeting compliance standards. A well-thought-out safety plan that addresses storage, handling, and upkeep is essential.

Location and Environment

Where you store diesel fuel matters - a lot. The right location can protect fuel quality and ensure safety. Keep fuel in cool, shaded areas, away from direct sunlight or heat sources, which can speed up fuel degradation and increase safety risks.

Storage containers need proper ventilation and should be kept far from ignition sources like open flames, electrical equipment, or direct sunlight. Maintain at least 50 feet of clearance from such hazards . If you're using above-ground tanks, be sure to follow local building codes and avoid high-traffic areas like driveways or forklift routes. If placement in these areas is unavoidable, install barriers or bollards to protect the tanks from accidental impacts.

OSHA provides clear guidelines for fuel storage. For indoor storage, any amount over 25 gallons must go into fire-resistant cabinets. Outdoor storage piles should not exceed 1,100 gallons, with at least 5 feet of space between piles and 20 feet of clearance from buildings.

Security is another key factor. Use locks, fencing, and clear markings to secure storage areas, reducing the risk of accidents or theft.

Once the location is set, ensure safe practices during refueling to protect workers and equipment.

Refueling Safety Procedures

When refueling, safety starts with turning off generators and restricting the task to trained personnel. This helps reduce the risks of fire or explosion . Smoking and open flames are strictly prohibited in storage areas.

Fire safety equipment is a must. A fire extinguisher rated at least 10B should be available within 50 feet of any area where more than 5 gallons of flammable liquids are handled. Regular checks and maintenance of fire suppression tools ensure they're ready when needed.

Proper labeling and handling of containers can prevent confusion and reduce accidents. Always use approved containers designed for flammable liquids. Secondary containment systems or double-walled tanks can prevent spills from contaminating soil or groundwater.

Generator placement is another critical consideration. Position generators so they don’t block building exits or interfere with fire department access. They should also be isolated and secured using fencing or enclosures to prevent unauthorized access.

Inspection and Maintenance

Safe storage doesn’t stop at setup - routine inspections and maintenance are just as important. Monthly visual checks for damage, along with leakage tests, can catch small problems before they become serious hazards. More detailed tests, like ultrasonic and pressure testing, should be done every five and ten years, respectively, to ensure the tanks remain in good condition.

Ultrasonic testing measures tank wall thickness and identifies corrosion or thinning. Pressure tests check for leaks or structural weaknesses. Monthly or quarterly leakage tests focus on tank walls and piping connections to detect and address any leaks early.

Other maintenance tasks include cleaning tanks and pipelines, tightening fittings, and applying protective coatings to fight corrosion. Fuel polishing and quality monitoring help keep the fuel in top shape, ensuring your generators perform reliably.

Inspection Type Frequency Purpose Key Focus Areas
Visual Inspection Monthly/Quarterly Detect exterior damage Corrosion, dents, loose fittings
Leakage Testing Monthly/Quarterly Identify leaks Tank walls, piping connections
Ultrasonic Testing Every 5 years Measure wall thickness Structural integrity, corrosion
Pressure Testing Every 10 years Check for weaknesses Overall tank structure

Keep detailed records of all inspections, repairs, and maintenance for regulatory compliance and future reference. Train your team on safety protocols and inspection procedures to ensure long-term reliability and safety.

"Acknowledging and adhering to OSHA fuel storage requirements is not just about compliance - it's about protecting the safety and well-being of employees and safeguarding business assets. By following these guidelines and best practices, employers can create a safer work environment and overcome potential hazards associated with fuel storage."

sbb-itb-501186b

Emergency Planning and Fuel Management

Having a solid fuel management plan in place can make all the difference during disasters. Consider this: 40% of small businesses never reopen after a major disaster because they weren’t prepared. By combining emergency measures with proper storage, quality control, and safety protocols, you can ensure your generators are ready when you need them most. A well-rounded fuel strategy should account for extended outages, supply chain issues, and severe weather disruptions.

Fuel Supply Planning

Emergency planning builds on good storage practices, ensuring fuel is available when demand spikes. For example, a diesel generator typically burns about 7 gallons of fuel per hour for every 100 kW of power. A 200 kW generator, therefore, consumes roughly 14 gallons per hour.

Your fuel reserves must cover both emergency operations and routine testing. Healthcare facilities following NFPA 99 regulations are required to maintain a minimum of 96 hours of usable fuel supply.

"When your operations hit a critical point, the last thing you need is a fuel shortage. Emergencies demand quick and reliable solutions, especially when powering essential equipment." - Jacobus Energy

To ensure fuel availability, diversify your supplier list and keep their contact details updated . Technology can also play a big role here. Use fuel level monitoring systems that send alerts before hitting critical levels. Additionally, fuel rotation schedules help prevent issues like degradation, ensuring the fuel in storage is always ready for use. Establish a clear threshold for reordering fuel based on your daily consumption patterns.

Load Management for Efficiency

Effective load management can stretch your fuel supply during shortages. Start by calculating your fuel needs for both average and peak load periods. Since a generator’s wattage rating determines its power output, it directly influences fuel consumption.

Plan ahead by identifying essential systems that must remain operational and temporarily cutting power to non-critical loads. Timing is also important - stagger energy-intensive activities to balance fuel usage more effectively.

Running generator load tests under real-world conditions is a great way to evaluate your fuel management strategies. Erik Bjornstad, host of the Fuel Pulse Show Podcast, explains:

"This kind of thing or these kinds of things like whether your entire power redundancy chain works as opposed to just the generator, that can really only be confirmed under this kind of full load test scenario, and this is the time for you to make it happen. This is the calm before the upcoming storms."

Good load management doesn’t just save fuel - it also ensures you maintain accurate operational records, which are essential for compliance.

Compliance and Record Keeping

Keeping detailed records isn’t just about staying organized - it’s a legal requirement. Failing to comply with OSHA’s standards, for instance, can result in fines of up to $70,000 per violation.

NFPA 110 standards require thorough documentation of all inspections, tests, and maintenance tied to your fuel system. Nearly every generator engine requires detailed operational logs, which are critical during regulatory inspections or when filing insurance claims.

Your compliance records should include key details like engine specifications, federal requirements, EPA Family Number, operational limits, and local environmental regulations. Some states also have specific rules for RICE (Reciprocating Internal Combustion Engine) engines, including air permitting requirements.

Fuel testing is another essential task and should be conducted every 3–6 months. This is particularly important for smaller storage tanks, which are more prone to issues like condensation and microbial growth. Maintain records of water contamination levels, microbial activity, and any signs of fuel degradation.

In March 2023, RILA updated the Emergency Generator Permitting Matrix, outlining state-specific permitting requirements for emergency generators. These regulations depend on local air quality standards and the overseeing regulatory agency. Regular audits and proper staff training can help you avoid costly violations. Develop a structured approach to compliance, including frequent reviews of your emergency fuel policies to keep them aligned with your operational needs.

Documentation Type Frequency Key Requirements Regulatory Source
Fuel Quality Testing 3–6 months Water levels, microbial growth, degradation NFPA 110
Generator Operation Logs Every operation Runtime, load, fuel consumption Federal/State
Inspection Records Monthly/Quarterly Tank condition, safety systems OSHA
Maintenance Documentation As performed Repairs, parts replacement, testing NFPA 110

"Effective emergency diesel fuel delivery management ensures your operations remain uninterrupted and efficient." - Jacobus Energy

Storage Solutions and Equipment Sources

Once you've established safe storage practices and ensured fuel quality, the next step is choosing the right storage equipment. Finding diesel storage solutions that align with your specific needs and available tools is crucial. With 84% of companies acknowledging room for improvement in fuel storage and management, selecting the right storage system and dependable suppliers is essential to keep your generator operations running smoothly.

Storage Solution Types

Sub-base tanks are a compact option, especially for smaller operations. These tanks sit directly beneath the generator set, featuring double-walled construction to prevent spills. Their integrated design saves space and reduces the need for additional fuel lines.

Underground tanks are designed for durability, as they're shielded from environmental factors, giving them a longer lifespan. However, they come with higher installation costs. These tanks require specialized spill prevention equipment and continuous monitoring systems to detect leaks early.

Above-ground tanks are easier to access but demand careful safety planning. They must be installed at specific distances from other facilities and require dikes to contain spills. Weather protection is a must, or alternatively, these tanks can be stored in fire-rated rooms that meet strict fire-resistance standards.

Day tanks act as intermediary storage between bulk diesel tanks and generator engines, ensuring a steady fuel flow during operation. These smaller tanks typically hold enough fuel for several hours, helping to maintain consistent fuel pressure.

Tank Type Capacity Range Key Advantages Main Considerations
Sub-base Under 1,000 gallons Space-efficient, integrated design Limited capacity, generator-specific
Underground 1,000+ gallons Long lifespan, environmental protection High installation cost, complex monitoring
Above-ground Variable Easy maintenance, lower cost Fire hazards, weather protection needed
Day tanks 50–500 gallons Consistent fuel flow, pressure regulation Requires bulk storage connection

When it comes to tank materials, steel tanks are strong and durable, making them suitable for outdoor use, though they are prone to corrosion. Aluminum tanks are lightweight and corrosion-resistant, making them a great choice for coastal areas. Polyethylene tanks offer excellent chemical resistance and are often a more affordable option.

After identifying the right tank type, the next step is sourcing high-quality equipment.

Equipment from Electrical Trader

Electrical Trader

Choosing the right storage solution is only part of the equation - reliable equipment is key to long-term performance. Electrical Trader connects buyers with both new and used diesel storage equipment designed for generator applications. Specializing in power generation tools and electrical components, the platform offers a one-stop shop for complete fuel storage systems.

New equipment available through Electrical Trader includes emergency standby diesel generators and storage components. These products meet current safety standards and come with full warranties, ensuring compliance with regulations like UL-142 and UL-2085. UL-142 tanks are suitable for general-purpose fuel storage in controlled environments, while UL-2085 tanks provide additional protection for higher-risk areas.

Used equipment is also an option for those looking to save on costs. Pre-owned tanks can serve reliably for years, as long as they meet safety standards and local regulations.

Electrical Trader’s categorized product listings make it easy to find specific components for a complete fuel storage system. Buyers can source secondary containment systems, fuel monitoring equipment, and corrosion-resistant coatings to ensure environmental safety. Other related components, such as fuel level sensors, transfer pumps, and monitoring systems, can also be purchased through the platform.

When choosing a tank, it's important to match its capacity to your fuel consumption and emergency needs. Under normal conditions, diesel fuel has a shelf life of 6–12 months. However, with proper storage and fuel treatments, this can extend to three years or more - a critical factor when deciding on tank size.

Electrical Trader’s marketplace model allows buyers to compare options from multiple sellers, ensuring competitive pricing and availability. The platform’s focus on electrical equipment also makes it easy to source both fuel storage tanks and the electrical components needed for efficient fuel management systems.

Summary

Storing diesel fuel for generators requires a thoughtful approach to tank sizing, fuel quality, safety measures, and emergency readiness. By addressing these aspects, you can ensure your generator performs dependably when it’s needed most.

For tank sizing, start by calculating your generator's fuel consumption and include a safety margin. Keep in mind that only about 80% of a tank's capacity is usable due to fuel expansion. Tank types include above-ground tanks (easy to monitor but may need protective enclosures), sub-base tanks (typically holding up to 1,000 gallons with double-walled designs), and underground tanks (offering longer lifespans but with higher installation costs). Alongside sizing, maintaining fuel quality is just as important.

To keep fuel in optimal condition, regular testing, using appropriate additives, and employing effective filtration are key. Diesel #2, for example, delivers more energy but can gel in cold weather. Adding fuel polishing to your routine maintenance can combat fuel degradation over time.

Storage safety is another critical factor. Choose appropriate storage locations, install spill containment systems, and schedule inspections to meet local regulations. Avoid filling tanks to full capacity to allow for fuel expansion and reduce the chances of spills.

Preparing for extended outages requires a solid strategy. Conduct risk assessments, establish a fuel rotation schedule, and implement a detailed fuel management plan. Aaron Rogerson of Foster Fuels highlights the importance of preparation:

"The best weapon against emergencies is preparedness. Prepare for power outages with a backup generator and plenty of emergency fuel solutions in place".

To round out your storage setup, companies like Electrical Trader offer UL-compliant storage solutions tailored for generator use. Their inventory includes secondary containment systems, fuel monitoring tools, and electrical components to help you meet current safety standards.

Since most generators don’t run continuously at full load, stored fuel often lasts longer than anticipated. When paired with proper storage techniques and quality equipment, this ensures a dependable fuel system that supports your generator during both routine use and emergencies.

FAQs

What are the best ways to extend the shelf life of diesel fuel for generators?

To keep diesel fuel for generators in good condition for longer, focus on proper storage and maintenance. Start by keeping the fuel in a cool, dark, and dry place to limit exposure to heat, light, and moisture - factors that can break down fuel quality over time. Use airtight, durable storage tanks to prevent contamination and slow down oxidation.

Incorporate fuel stabilizers into your maintenance routine. These additives are designed to slow oxidation, prevent microbial growth, and reduce chemical degradation, potentially extending the fuel's shelf life to 18–24 months. Regular inspections of your storage tanks are equally important - look for water buildup or contamination. If microbial growth becomes an issue, biocides can help keep the fuel clean and effective.

By pairing smart storage practices with the right additives, you can extend the usability of diesel fuel and ensure your generator is ready whenever you need it.

What should I consider when deciding between above-ground and underground diesel storage tanks for my generator?

When deciding between above-ground and underground diesel storage tanks, it’s essential to weigh factors like cost, maintenance, available space, and security to find the best fit for your needs.

Above-ground tanks are often the cheaper option and are easier to install. Their design allows for quick visual inspections, making them a practical choice for locations with plenty of space. Maintenance and repairs are simpler with these tanks, but they can be more exposed to weather conditions and potential tampering.

On the flip side, underground tanks save surface space, enhance the site's appearance, and provide better protection against theft or vandalism. That said, they come with higher installation and maintenance costs due to the need for excavation and adherence to stricter regulations. Your final decision should align with your site requirements, budget, and long-term plans.

How can I maintain diesel fuel quality and prevent issues like water contamination or microbial growth in storage tanks?

To keep diesel fuel in good condition and prevent issues like water contamination and microbial growth, reducing water in storage tanks is key. Make it a habit to check for water at least twice a year and try to keep tanks as full as possible - this helps cut down on condensation. Regularly inspect tanks for water and sludge buildup, and consider using diesel additives that can help disperse water and curb microbial growth.

It’s also wise to store diesel fuel in a cool, dry location, away from direct sunlight. If you plan to store the fuel for more than 30 days, adding stabilizers can help preserve its quality. These precautions will keep your fuel in top shape, ensuring it’s ready to power your generator when needed.